Vacuuming And Charging
Purging The Piping And Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant R22, the indoor unit and the refrigerant
connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle
may cause malfunction of the compressor.
Make sure all pipes are connected securely to the outdoor and indoor valves.
Remove the caps from the are valve and the service. Take note that there are a total of two service ports
for M5MSX020A/AR, three service ports for M5MSX025A/AR and four service ports for M5MSX030A/AR.
Connect the center of the charging gauge to the vacuum pump.
Starting from the bottom 3-way valve (labeled A), connect the charging gauge to the 3-way valve’s service
port. (The numbers of service ports depend on the O/D unit model).
Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different
vacuum pump capacity. Conrm that the charging gauge needle has moved towards -760mmHg.
Proceed to the next 3-way valve and repeat the steps above.
Caution
If the gauge needle does not move to - 760mmHg, be ure to check for gas leaks (using the refrigerant
detector) at are type connection of the indoor and outdoor unit and repair the leak before proceeding
to the next step.
Close the valve of the charging gauge and stop the vacuum pump.
On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with
4mm key for hexagon sacked screw.
Additional Charge
The refrigerant is pre-charged in the outdoor unit for specic piping length. Please refer to page 1-5 for further
detail on additional charge.
Service Port
Outdoor Unit 3 ways valve
Flare nut
Refrigerant Piping
Allen key
Suction
valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Vacuum
pump
Open
Close
Close
Close
Hi
Low
Application Information