McQuay M4LC Especificaciones Pagina 74

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 269
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 73
PP
PP
P
erferf
erferf
erf
oror
oror
or
mance Damance Da
mance Damance Da
mance Da
tata
tata
ta
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC at
those temperatures which are not stated out in the table.
Example:
Model: MCM 020D– MLC 020B
Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Solution:
Overall
Based on the Performance table on Pg.98
1. Refer to the Indoor DB column,
- 23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C WB
and 17°C WB during 24°C indoor DB is required)
3. Refer to the Outdoor DB column,
- 37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
3
r
d
Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor: 23°C DB, 15°C WB
Outdoor:
37°C DB
2
n
d
Step
Interpolation of Indoor DB
Find TC, SC for
(a) Indoor:
23°C DB
, 15°C WB
Outdoor: 35°C DB
(b) Indoor:
23°C DB
, 15°C WB
Outdoor: 40°C DB
1
s
t
Step
Extrapolation of Indoor WB
Find TC, SC for
(a) Indoor: 24°C DB,
15°C WB
Outdoor: 35°C DB
(b) Indoor: 24°C DB,
15°C WB
Outdoor: 40°C DB